Danfoss VLT AutomationDrive FC 302 · Alarm WARNING/ALARM 2: Live zero error
What it means An analog input signal is below 50% of its programmed minimum, indicating live-zero loss or an input/wiring problem.
✓ Checked against the manual (Oct 2026): code and name match the official manual, printed page 84.
Troubleshooting
Troubleshooting steps for this code sit behind a short safety notice. Read it before you open them.
Troubleshooting
Safety first
Before troubleshooting: shut down the equipment, isolate every energy source, lock and tag the energy-isolating devices, release or restrain stored energy, and verify by try-out that all energy is neutralized before work begins.
Follow your site’s written energy-control procedure and the manufacturer’s manual. This is general information only and does not replace a qualified person, site safety requirements, or OSHA requirements.
Check analog-input wiring and terminals 53/54 or the installed analog-I/O option.
Verify the programmed signal type and live-zero parameters.
Test the input signal and connected transmitter with the equipment isolated as required.
Source
Name as printed in the official Danfoss manual for the VLT AutomationDrive FC 302, printed page 84. Meaning and checks are reworded, not copied. Official manual (PDF). Codes and names can differ between firmware versions.