Danfoss VLT AutomationDrive FC 302 · Alarm WARNING/ALARM 26: Brake resistor power limit
What it means Average braking dissipation exceeded the monitored brake-resistor limit; with Trip selected, the converter trips at 100%.
✓ Checked against the manual (Oct 2026): code and name match the official manual, printed page 86.
Troubleshooting
Troubleshooting steps for this code sit behind a short safety notice. Read it before you open them.
Troubleshooting
Safety first
Before troubleshooting: shut down the equipment, isolate every energy source, lock and tag the energy-isolating devices, release or restrain stored energy, and verify by try-out that all energy is neutralized before work begins.
Follow your site’s written energy-control procedure and the manufacturer’s manual. This is general information only and does not replace a qualified person, site safety requirements, or OSHA requirements.
Review braking duty and parameter 2-13 Brake Power Monitoring.
Check for excessive regeneration or too-short deceleration.
Source
Name as printed in the official Danfoss manual for the VLT AutomationDrive FC 302, printed page 86. Meaning and checks are reworded, not copied. Official manual (PDF). Codes and names can differ between firmware versions.