What it means The brake IGBT has short-circuited or the brake circuit is otherwise faulted; the brake is disabled and substantial power may reach the resistor.
✓ Checked against the manual (Oct 2026): code and name match the official manual, printed page 86.
Troubleshooting
Troubleshooting steps for this code sit behind a short safety notice. Read it before you open them.
Troubleshooting
Safety first
Before troubleshooting: shut down the equipment, isolate every energy source, lock and tag the energy-isolating devices, release or restrain stored energy, and verify by try-out that all energy is neutralized before work begins.
Follow your site’s written energy-control procedure and the manufacturer’s manual. This is general information only and does not replace a qualified person, site safety requirements, or OSHA requirements.
Remove power and inspect the brake circuit and resistor.
Check brake resistor overheating and Klixon inputs where fitted.
For 12-pulse units, check disconnects or breakers that may have opened while energized.
Source
Name as printed in the official Danfoss manual for the VLT AutomationDrive FC 302, printed page 86. Meaning and checks are reworded, not copied. Official manual (PDF). Codes and names can differ between firmware versions.