Siemens SINAMICS G120 F01910: Fieldbus interface setpoint timeout
What it means The drive stopped receiving setpoints over the fieldbus.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Bus connection interrupted
- Communication partner switched off
- PROFIBUS master in STOP
Checks, in order
- Check the bus connection and switch on the partner
- Check PLC state
- Adapt p2040 if needed
Source
Source (reworded, not copied): Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, 02/2023, A5E33839529, section 4.2 List of faults and alarms, PDF page 861. Official manual (PDF). Fault numbers and names can differ between firmware versions.