Siemens SINAMICS G120 F30011: Power unit: Line phase failure in main circuit
What it means DC link voltage ripple went over the allowed limit, usually because a line phase is missing or badly unbalanced.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Failed line phase
- Blown main circuit fuse
- Badly unbalanced phases
- Failed motor phase
Checks, in order
- Check the main circuit fuses
- Measure all input phases
- Check for a single-phase load distorting the line
Source
Source (reworded, not copied): Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, 02/2023, A5E33839529, section 4.2 List of faults and alarms, PDF page 906. Official manual (PDF). Fault numbers and names can differ between firmware versions.