Allen-Bradley PowerFlex 525 F002: Auxiliary Input
What it means An external trip (auxiliary) input told the drive to stop.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Opened safety/interlock contact wired to an input set as aux fault
- Wrong input configured
- Loose wire
Checks, in order
- Find which input is set as aux fault
- Check that remote wiring
- Check communication programming for an intentional fault
Old Hand tip
Nine times out of ten it's a door switch or E-stop chain, not the drive.