Allen-Bradley PowerFlex 525 F029: Analog In Loss
What it means An analog input that is set to fault on signal loss lost its signal.
✓ Checked against the manual (Oct 2026): meaning and actions match the official fault table. Manual page.
Likely causes
- Broken 4-20 mA or 0-10 V wire
- Failed transmitter
- Loss setting (t094 or t097) not what you expect
Checks, in order
- Check for broken or loose connections at the inputs
- Measure the signal at the terminals
- Check t094 and t097
Source
Source (reworded, not copied): Rockwell Automation, PowerFlex 520-Series AC Drives User Manual, publication 520-UM001O-EN-E (September 2025), Chapter 4 Troubleshooting, PDF page 161. Official manual (PDF). Fault numbers and names can differ between firmware versions.